- Home
- FirePro
- Access Floor Void
- • FirePro® Access Floor Firestop
• FirePro® Access Floor Firestop
- General Details
As part of the comprehensive FirePro® range of fire protection products, Fire-Pro® Access Floor Firestop is a specifi-cally developed product, designed to provide cavity fire stops for use in voids between raised access floors and the floor slabs. The product has been designed as a one-piece system and affords easy cutting and installation. It offers unique lateral compression to allow tightness of fit.
The product is available in two versions:
AF 30; giving 30 minutes fire resistance.
AF 60; giving 60 minutes fire resistance.
Advantages
- Easy to cut and install
- Ensures site tolerances are accommodated
- Tested over 60 minutes fire resistance
- Resists the passage of smoke
- Suitable for cavity widths up to 600mm
- Excellent acoustic performance
- Excellent lateral compression
- Available is slabs or strips
- Technical Info
Standards and approvals
FirePro® AF 30 and AF 60 Access Floor Firestops have been tested and assessed in accordance with BS 476: Part 20 1987 and have achieved 30 minutes and 60 minutes fire insulation and integrity respectively. Please refer to LPC Test Report
TE 91727 and Assessment number CC91988.Performance
Fire
The base stone wool of FirePro® Access Floor Firestop is inherently non-combustible. Rockwool products will
withstand temperatures in excess of 1000°C.Acoustic
When used below access floors FirePro® Access Floor Firestops will reduce appreciably the levels of airborne
sound transmission through the floor cavity.Resistance to moisture
FirePro® Access Floor Firestops are water repellent.